Three-Phase Systems, Transformers & Machines

Balanced three-phase power, wye/delta relations, transformer ratings, induction-motor speed. Power systems depth

Balanced three-phase

  • P = √3 V_L I_L cosθ, Q = √3 V_L I_L sinθ, S = √3 V_L I_L.
  • Wye: V_L = √3 V_ph, I_L = I_ph. Delta: V_L = V_ph, I_L = √3 I_ph.

Transformers

  • Voltage ratio ≈ turns ratio a = N₁/N₂. Rated currents from kVA: I = S/V (single phase).
  • Impedance referred to the primary = a² × secondary impedance.

Induction machines

  • Synchronous speed n_s = 120f/P (P = poles). Slip s = (n_s − n)/n_s, rotor speed n = n_s(1 − s).